Weil-McLain Combi Boiler: Boiler fires or pumps run with no call for heat
Boiler fires or pumps run with no call for heat on a Weil-McLain combi boiler: Two built-in functions can do this. Freeze protection starts the chosen circulators when the heat exchanger sensors drop below 45°F, fires the burner at low fire below 40°F, and stops both above 48°F. Circulator exercising runs each selected pump for 10 seconds after 72 hours with no run time.
Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)
Common causes of boiler fires or pumps run with no call for heat
- Freeze protection active
- Circulator exercising
How to fix boiler fires or pumps run with no call for heat: step by step
- Check boiler water temperature on the information screen. Low readings near 40-48°F point to freeze protection.
- Look at contractor menu > Pump Settings > Freeze Protect Circs and Circulator Exercising to see which pumps are set.
- A 10-second pump run after a long idle period is the exercise function, not a fault.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Pump Settings, p.59. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.