Weil-McLain Boiler: Zoning with zone valves, two zones (no DHW)
Zoning with zone valves, two zones (no DHW) on a Weil-McLain boiler: Two space heating zones with zone valves. INPUT 1 is reserved for the system circulator, so it cannot be used for a wired thermostat. The system must have a bypass pressure regulating valve because flow can occur with all zone valves closed.
Applies to: SF1000L/R, SF1500L/R, SF2000L/R
How to fix zoning with zone valves, two zones (no dhw): step by step
- Wire thermostats to INPUT 2 and INPUT 3 and keep both on PRIORITY 2.
- Assign INPUT 1 to AUX PUMP/OUTPUT.
- Select ANY INPUT BY ITS PRIORITY as the activation condition so the system pump runs on any zone call.
- Confirm PRIORITY 2 RUN AUX PUMP/OUT is set to YES.
- Install a bypass pressure regulating valve in the system.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 61. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.