Weil-McLain Boiler: Zoning with zone valves: two space heating zones (no DHW)
Zoning with zone valves: two space heating zones (no DHW) on a Weil-McLain boiler: Two thermostats on Inputs 2 and 3. Input 1 runs the system circulator through AUX PUMP/OUTPUT.
Applies to: SlimFit Series 3 with zone valves
How to fix zoning with zone valves: two space heating zones (no dhw): step by step
- Review the 120 VAC output wiring (p. 60) and 24 VAC input wiring (p. 52).
- Wire thermostats to Inputs 2 and 3. Keep both on PRIORITY 2 and choose the space heating system type.
- Assign Input 1 to AUX PUMP/OUTPUT. Select ANY INPUT BY ITS PRIORITY when prompted for activation.
- Confirm that Priority 2 RUN AUX PUMP/OUT is set to YES so the system pump runs when either zone calls.
- Do not wire a thermostat to Input 1 (P11-4/5), since it is used for the system circulator.
- Use the factory defaults for the system type, or change if needed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SlimFit Series 3 boiler manual, p. 65. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.