Weil-McLain Boiler: Zoning with circulators: three space heating zones plus indirect DHW piped to boiler
Zoning with circulators: three space heating zones plus indirect DHW piped to boiler on a Weil-McLain boiler: Three space heating zones and one indirect DHW aquastat on the boiler control.
Applies to: SVF 500/600 boilers with indirect DHW tank
How to fix zoning with circulators: three space heating zones plus indirect dhw piped to boiler: step by step
- Review the wiring in Sections B and C (pages 72 and 73).
- Wire the DHW aquastat to Input 1 (J17-1/2).
- Wire space heating thermostats to Inputs 2, 3 and 4.
- Assign Inputs 2, 3 and 4 to PRIORITY 2 and choose the matching heating system type in the Wizard or in the PRIORITY 2 menu.
- Assign Input 1 to PRIORITY 1 so DHW takes precedence.
- Use the factory default DHW and heating system settings, or change them if needed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 500/600 Series 1 boiler manual, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.