Weil-McLain Boiler: Zoning: four space heating zones, no indirect DHW
Zoning: four space heating zones, no indirect DHW on a Weil-McLain boiler: Each of the four input and output pairs runs one heating zone with its own thermostat and circulator or zone valve.
Applies to: SVF 500/600 Series 1 boilers
How to fix zoning: four space heating zones, no indirect dhw: step by step
- Wire the zone thermostats to Input 1 (J17 1 and 2), Input 2 (J17 4 and 5), Input 3 (J17 7 and 8) and Input 4 (J16 1 and 2).
- Wire circulators or 120 Vac zone valves to Outputs 1 to 4 as shown in the zoning diagram.
- Choose the space heating system type during the Wizard, or set it manually in the PRIORITY 2 menu of System Settings.
- Keep the factory default settings for the chosen system type, or change them if needed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF 500/600 Series 1 boiler manual 550-100-273/1224, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.