Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Weil-McLain Boiler: Zone valve zoning with variable primary flow

Updated · by Aurora Star Tech Inc.

Zone valve zoning with variable primary flow on a Weil-McLain boiler: For systems that use a variable-flow system pump. Figure 15 shows DHW as a zone. Figure 16 shows optional DHW piping. Check the general zone valve zoning page (p. 23) first.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SVF 500/600 boilers with variable primary flow pumping

How to fix zone valve zoning with variable primary flow: step by step

  1. Install a system circulator capable of the variable flow and head required.
  2. Install the flow/check valve on the boiler outlet to prevent gravity circulation during DHW heating.
  3. If a bypass is used (differential pressure valve or pressure reducing valve), place the system supply temperature sensor after the bypass.
  4. Install a flow switch if system flow could drop below the minimum flow in the Table 5 specification (p. 21 referenced; table is not on these pages).
  5. Install a tee for the flow switch on the boiler return pipe.
  6. Use a bypass pressure regulator or pressure reducing valve in high-flow systems to prevent excessive flow through the heat exchanger.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF 500/600 Series 1 Boiler Manual, p. 25. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977