Weil-McLain Boiler: Zone valve zoning with high-flow DHW circuit (primary/secondary)
Zone valve zoning with high-flow DHW circuit (primary/secondary) on a Weil-McLain boiler: Use when the DHW circuit needs more flow than the boiler allows, or with a high pressure-drop coil-type DHW tank. DHW flows only through the secondary connection piping, which keeps the boiler circulator head off the zone valves.
Applies to: SF-550 and SF-750
How to fix zone valve zoning with high-flow dhw circuit (primary/secondary): step by step
- Size the primary/secondary connection piping (Fig. 8, item 23) for the full flow it must carry.
- Install a system circulator sized for the required flow and head.
- Fit a flow/check valve on the boiler outlet to stop gravity circulation during DHW heating.
- Pipe all boiler loop runs at least to the minimum pipe size in Figure 4 (p. 13).
- Provide a system expansion tank per p. 14. Do not use a closed-type tank if the DHW heater has an automatic vent.
- Set DHW and space heating priorities: DHW on Priority 1 with space heating on 2 and/or 3, or space heating on 1 and/or 2 with DHW on 3. The control never runs two priorities at once.
- For more than 3 zones, use the WMZV zone valve controller.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.