Weil-McLain Boiler: Zone valve zoning, high flow or high head DHW circuits
Zone valve zoning, high flow or high head DHW circuits on a Weil-McLain boiler: Use when DHW circuit flow exceeds boiler limits or when a coil-type DHW tank has high pressure drop. DHW water flows only through the secondary connection piping. Size the connection piping for the total flow it must carry.
Applies to: DHW zone valve piping
How to fix zone valve zoning, high flow or high head dhw circuits: step by step
- Size the DHW secondary connection piping (item 23) for the total flow.
- Install a system circulator that delivers the required flow and head.
- Install the flow/check valve on the boiler outlet piping to prevent gravity circulation during DHW heating.
- Keep connection tees no more than eight pipe diameters apart.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 500/600 Series 1 boiler manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.