Weil-McLain Boiler: WMCR circulator zone controller plus boiler-controlled DHW
WMCR circulator zone controller plus boiler-controlled DHW on a Weil-McLain boiler: DHW is piped directly to the boiler. The zone controller calls for space heating on INPUT 2. A relay with a normally closed contact interrupts the zone controller's ZC-ZR 120 VAC circuit during DHW operation so space heating stops while DHW runs.
Applies to: SF1000L/R, SF1500L/R, SF2000L/R
How to fix wmcr circulator zone controller plus boiler-controlled dhw: step by step
- Provide relay R1 with a 120 VAC coil and an NC contact.
- Wire R1 to interrupt the zone controller's ZC-ZR 120 VAC operating circuit.
- Connect the zone controller call for heat (X-X) to INPUT 2 and keep INPUT 2 on PRIORITY 2.
- Wire the DHW aquastat to INPUT 1 and assign INPUT 1 to PRIORITY 1.
- Wire the DHW circulator to OUTPUT 1.
- Set the heating system type in PRIORITY 2 as required.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.