Weil-McLain Boiler: Wire the system supply and return sensors
Wire the system supply and return sensors on a Weil-McLain boiler: Two strap-on sensors are required for proper control. If the return reads hotter than the supply, the control reports a sensor fault.
Applies to: SlimFit 550/750 Series 3 boiler
Common causes of wire the system supply and return sensors
- Sensor not installed or installed incorrectly
- Return temperature reads above supply temperature
How to fix wire the system supply and return sensors: step by step
- Strap one sensor to the system supply piping and one to the return piping.
- Place the supply sensor at least six pipe diameters, and no more than 3 feet, downstream from the boiler connection to the main.
- Use immersion sensors on piping larger than 5 in. diameter or on nonmetallic piping for faster response.
- Wire the supply sensor to P14 pins 1 and 2, and the return sensor to P14 pins 3 and 2.
- Thermostat wire can be used for these sensors.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 3 boiler manual, p. 53. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.