Weil-McLain Boiler: Wire room thermostats, aquastats and zone valves
Wire room thermostats, aquastats and zone valves on a Weil-McLain boiler: Inputs are dry contacts only. Supplying 24 V to the thermostat circuits can damage the control.
Applies to: Inputs 1, 2 and 3 and their terminal strips
How to fix wire room thermostats, aquastats and zone valves: step by step
- Do not supply 24 VDC or 24 VAC power to the thermostat or input circuits.
- Wire Input 1 to P11 terminals 4 and 5, Input 2 to P15 terminals 1 and 2, and Input 3 to P15 terminals 3 and 4.
- If a thermostat needs continuous 24 V, connect its common wire to P11 pin 2 and keep total draw within limits.
- For 3-wire zone valves, use relays to provide dry contacts to the control inputs.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 53. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.