Weil-McLain Boiler: Wire external limits for manual or automatic reset
Wire external limits for manual or automatic reset on a Weil-McLain boiler: Factory jumper must be removed before a external limit is wired. Manual reset lockout needs a person at the boiler to reset. Cycling power does not reset a manual lockout.
Applies to: External limit inputs, terminal block P13
Common causes of wire external limits for manual or automatic reset
- Limit circuit opens during operation
How to fix wire external limits for manual or automatic reset: step by step
- Remove the factory jumper on the chosen circuit.
- For manual reset, wire isolated limit contacts across P13 pins 1 and 2.
- For manual reset, the control locks out and the alarm contacts close when the limit opens.
- Reset manually using the procedure in this manual after the limit closes.
- For automatic reset, wire isolated limit contacts across P13 pins 3 and 4.
- For automatic reset, the burner shuts down when the limit opens and restarts 150 seconds after the limit closes.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 55. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.