Weil-McLain Boiler: Water chiller piping (zone valves, primary/secondary)
Water chiller piping (zone valves, primary/secondary) on a Weil-McLain boiler: The chiller is piped in parallel with the boiler and must be kept from the boiler loop.
Applies to: SF-550 and SF-750
How to fix water chiller piping (zone valves, primary/secondary): step by step
- Pipe the chiller in parallel with the boiler.
- Install valves so chilled medium cannot enter the boiler.
- If the heating coils sit in air handlers exposed to refrigerated air, use flow control valves or another automatic method to stop gravity circulation during cooling.
- Use only antifreeze listed by WM Technologies for this boiler. Consider antifreeze effects on circulator sizing and DHW performance.
- If local code requires, use a double-wall DHW heat exchanger.
- Optional circulator zoning needs a separate circulator for the chilled loop and one per zone.
- Provide the expansion tank and flow/check valve as in the other layouts.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.