Weil-McLain Boiler: Water chemistry and inhibitor check
Water chemistry and inhibitor check on a Weil-McLain boiler: Weil-McLain recommends adding Sentinel X100 inhibitor to protect the heat exchanger. Check water chemistry after filling and leak testing, and again at least once a year. Water pH must stay between 7.0 and 8.5, or the inhibitor test kit must show an acceptable level.
Applies to: SlimFit Series 2 boilers
Common causes of water chemistry and inhibitor check
- Residual substances left in the system after filling
- Low inhibitor level or pH outside 7.0 to 8.5
How to fix water chemistry and inhibitor check: step by step
- After filling and leak testing, check water pH and chlorine concentration.
- Add X100 inhibitor by caulking gun or in liquid form, following the container instructions.
- Let the water circulate, then test the inhibitor level with the Sentinel test kit and add more if needed.
- Each year, test pH of a system water sample; it must be 7.0 to 8.5.
- If pH is out of range or the test kit shows low inhibitor, correct the level before leaving the system.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.