Weil-McLain Boiler: Vertical direct vent termination with sidewall air inlet (Category IV)
Vertical direct vent termination with sidewall air inlet (Category IV) on a Weil-McLain boiler: Vent exits through the roof while the combustion air inlet exits through a sidewall, using a down-turned air elbow and a stop-plate assembly.
Applies to: SVF 500/600 Series 1 vertical direct vent with sidewall air
How to fix vertical direct vent termination with sidewall air inlet (category iv): step by step
- Keep the roof vent termination 12 in min above the roof or snow line and no more than 48 in above the roof.
- Cut the air pipe hole to the air pipe maker's size.
- Cut the vent pipe hole at least 3/8 in larger than the vent pipe diameter for combustible construction, or per the vent maker for noncombustible construction.
- Set a corrosion-resistant metal thimble in the vent hole and follow local code for isolating the pipe through floors, ceilings and roofs.
- Install corrosion-resistant stop plates from the vent pipe maker, with hole sizes just larger than the pipe, so the pipes cannot be pushed inward.
- Insert the last lengths of vent and air pipe from outside until the female-end shoulders rest on the outer stop plates.
- Attach the termination elbow to the air pipe end and fit a bird screen supplied by the vent maker in the open end of the termination.
- Brace the air pipe at no more than 24 in spacing and make sure the air pipe extends far enough through the wall for full engagement of the air elbow.
- Seal all exterior openings with exterior caulk.
- For multiple boilers, keep flue vents 6 in apart from other flue vents, air terminations 6 in apart from other air terminations, and flue vents 12 in horizontally from air terminations.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 500/600 Series 1 Boiler Manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.