Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Weil-McLain Boiler: Venting and combustion air setup requirements

Updated · by Aurora Star Tech Inc.

Venting and combustion air setup requirements on a Weil-McLain boiler: Each SlimFit needs its own vent. Vent and air piping must be airtight, follow the manual, and meet code. Use one of two methods: direct exhaust (room air) or direct vent (outside air piped in).

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SlimFit 1000-2000 Series 2

Common causes of venting and combustion air setup requirements

  • Common venting with another appliance
  • Leaking or obstructed vent or air piping
  • Contaminated combustion air
  • Insulated nonmetallic vent pipe

How to fix venting and combustion air setup requirements: step by step

  1. Do not common vent a Category IV boiler or any other appliance. Each boiler gets its own vent.
  2. Check any remaining appliances on the same common vent per page 26 (not on these pages).
  3. Inspect the finished vent and air piping for airtightness and code compliance.
  4. Confirm all air openings are the correct size, unobstructed and free of airborne contaminants.
  5. Do not cover nonmetallic vent pipe with thermal insulation.
  6. Provide combustion air per the National Fuel Gas Code or the applicable CSA B149.1 sections, or local code.
  7. For direct exhaust: take combustion air from the boiler room through openings, sized for all appliances sharing the space.
  8. For direct vent: pipe combustion air from outside, not terminating where contaminated air can enter. Manifolding is shown in Figure 31 (page 36).
  9. Use only the vent and air materials listed in Figure 22 (page 25).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SlimFit Series 2 Boiler Manual, p. 23. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977