Weil-McLain Boiler: Vent and air plate – wall hole layout and cutting
Vent and air plate - wall hole layout and cutting on a Weil-McLain boiler: Lay out and cut the wall holes for the Weil-McLain vent and air plate.
Applies to: SVF 500/600 Category IV direct vent, sidewall vent and air plate
How to fix vent and air plate - wall hole layout and cutting: step by step
- Place the template from the termination kit on the outside wall at the penetration spot and check for obstructions.
- Level the template. The flue and air pipes must come out side-to-side.
- Mark the four mounting holes, flue pipe and air pipe openings.
- Use a small long bit to drill centering holes first, then drill the large openings from inside and outside.
- Drill the air pipe opening 3-1/2 in diameter for a 3 in air pipe.
- For combustible wall material, drill the vent opening 4 in diameter for a 3 in vent pipe.
- For noncombustible wall material, drill the vent opening 3-1/2 in diameter for a 3 in vent pipe.
- If preferred, run both pipes through one rectangular cutout marked on the template.
- Make sure the outside and inside cover plates are oriented correctly. They are stamped for exhaust (vent) and intake (air).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 59. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.