Weil-McLain Boiler: Ultra-80 or Ultra-105 low output on 2-inch vent/air pipe
Ultra-80 or Ultra-105 low output on 2-inch vent/air pipe on a Weil-McLain boiler: The Ultra-80 and 105 allow 2-inch PVC vent and air pipe, but the boiler derates itself because of the extra pressure drop. Lower output is expected, not a fault.
Applies to: Weil-McLain Ultra-80 and Ultra-105 Series 3 gas boilers
Common causes of ultra-80 or ultra-105 low output on 2-inch vent/air pipe
- 2-inch vent and air pipe used on Ultra-80 or 105
- Long equivalent length or too many elbows
How to fix ultra-80 or ultra-105 low output on 2-inch vent/air pipe: step by step
- Check pipe size and total equivalent length. Max is 100 equivalent feet with the elbow limits in the guide.
- Count elbows: 7 ft each for 2 or 3 in. long-radius 90 or 45 elbows and 4 in. elbows; 16 ft each for 2 or 3 in. short-radius elbows.
- With 2-inch pipe at 100 ft, expect up to about 10% derate on the Ultra-80 and 15% on the Ultra-105.
- If the house needs full output, re-pipe in 3-inch (reducers per the guide).
- Concentric terminations: PVC schedule 40 only, no CPVC or ABS.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 3 Quick-Start installation guide and material checklists C-1120 (0910), vent/air piping length table. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.