Weil-McLain Boiler: Thermostat and dry contact heat demand wiring
Thermostat and dry contact heat demand wiring on a Weil-McLain boiler: Inputs 1 to 3 take dry contact calls for heat. They do not supply 24 V.
Applies to: SlimFit 550/750 Series 3 boiler
How to fix thermostat and dry contact heat demand wiring: step by step
- Wire thermostats, aquastats or end switches as dry contacts on Input 1, 2 or 3.
- If a thermostat needs continuous 24 V, connect its common wire to P11 pin 2 and keep total current per thermostat within its limit.
- For 3-wire zone valves, use relays to make dry contacts for the control inputs.
- Do not put 24 V from the boiler into any thermostat circuit.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 3 boiler manual, p. 52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.