Weil-McLain Boiler: SVF cascade: member boiler stops when it loses the master
SVF cascade: member boiler stops when it loses the master on a Weil-McLain boiler: In a cascade, a member boiler shuts down when it loses communication with the master unless it was set up to keep running. The wizard default is No.
Applies to: SVF 725, 850, 1000 (Series 1) and SVF 1500-3000 (Series 2)
Common causes of svf cascade: member boiler stops when it loses the master
- Boiler-to-boiler communication cable loose, damaged or wired wrong
- Master boiler off or its control down
- Member set to not run on lost communication
How to fix svf cascade: member boiler stops when it loses the master: step by step
- Check the master boiler is powered and running.
- Check the boiler-to-boiler communication cables (Section 3 wiring, p.67 / p.80).
- If the building needs heat even when the link is lost, set the member's "run if communication is lost" answer to Yes. It will then hold a fixed setpoint or the last setpoint from the master, whichever is chosen.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF 725/850, 1000 Series 1 / 1500-3000 Series 2 Advanced Installation Manual 550-143-071/0924, Express Setup Multi-Boilers notes, p.22-23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.