Weil-McLain Boiler: Steam relief valve popping
Steam relief valve popping on a Weil-McLain boiler: Water or steam keeps coming out of the relief valve.
Applies to: SGO-3 to SGO-9 oil-fired steam boilers
Common causes of steam relief valve popping
- Pressure limit control not working or set too high
- Wrong relief valve or a weak valve opening early
How to fix steam relief valve popping: step by step
- Turn the burner off if pressure is near 15 psi.
- Check the pressure control setting, its wiring and that it actually shuts the burner off. Replace it if it does not.
- Confirm the relief valve is rated 15 psi. If it opens below 15 psig, replace it.
- Test the pressure control: with the burner running, move the setting below the actual steam pressure. Burner must stop. Move it back up and the burner should relight.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Troubleshooting p.7; Check out procedure p.35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.