Weil-McLain Boiler: Startup screen shows OUTDOOR: NOT ATTACHED
Startup screen shows OUTDOOR: NOT ATTACHED on a Weil-McLain boiler: The control reports that no outdoor temperature sensor is connected. An outdoor sensor is required by federal rules unless the system is exempt.
Applies to: Evergreen Series 2 boilers, startup and BOILER SETTINGS
Common causes of startup screen shows outdoor: not attached
- Outdoor sensor not installed or not wired to the control
- System is exempt but the exemption was not set in the control
How to fix startup screen shows outdoor: not attached: step by step
- Check whether the system meets one of the exemption conditions listed in the manual.
- If not exempt, install and wire the outdoor sensor.
- If exempt, answer YES on the exemption prompt and set ODT SENSOR EXEMPT to YES in BOILER SETTINGS.
- Only set exempt when the boiler really qualifies. Exempt units cannot use WWSD.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 65, 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.