Weil-McLain Boiler: Sidewall termination clearances
Sidewall termination clearances on a Weil-McLain boiler: A sidewall termination must stay clear of door and window openings, roof overhangs, forced air intakes and other vent exit points. Do not terminate above a door or window or under a deck, since condensate can freeze.
Applies to: Direct exhaust sidewall termination
How to fix sidewall termination clearances: step by step
- Keep at least 6 ft from adjacent walls.
- Keep at least 5 ft below any roof overhang.
- Keep at least 3 ft above any forced air intake within 10 ft.
- Keep at least 48 in below or horizontal from any door, window or gravity air inlet.
- Do not terminate above a door or window or under a deck.
- Do not place the termination where plume or condensate will damage shrubs, air conditioners or building surfaces.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.