Sidewall termination clearances on a Weil-McLain boiler: A sidewall termination must stay clear of door and window openings, roof overhangs, forced air intakes and other vent exit points. Do not terminate above a door or window or under a deck, since condensate can freeze.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Direct exhaust sidewall termination

How to fix sidewall termination clearances: step by step

  1. Keep at least 6 ft from adjacent walls.
  2. Keep at least 5 ft below any roof overhang.
  3. Keep at least 3 ft above any forced air intake within 10 ft.
  4. Keep at least 48 in below or horizontal from any door, window or gravity air inlet.
  5. Do not terminate above a door or window or under a deck.
  6. Do not place the termination where plume or condensate will damage shrubs, air conditioners or building surfaces.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 32. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.