Weil-McLain Boiler: Set up 0-10 VDC remote target temperature control
Set up 0-10 VDC remote target temperature control on a Weil-McLain boiler: Uses a 0-10 VDC signal to set the supply target temperature instead of the outdoor sensor.
Applies to: SF-550 and SF-750 single boiler installations
How to fix set up 0-10 vdc remote target temperature control: step by step
- Wire the 0-10 VDC signal to P15 pin 6 (positive) and pin 5 (common).
- Connect at least one dry contact heat demand to an unused input. Assign it to a priority in the Wizard or the contractor menu.
- On the priority used for heating (PRIORITY 2 for single boilers), set TARGET ADJUST to 0-10V.
- Set VOLTS FOR MAX to the voltage that calls for the highest target and set SUPPLY MAX to that temperature.
- Set VOLTS FOR MIN to the voltage that calls for the lowest target and set SUPPLY MIN to that temperature.
- Between the two voltages, the target scales linearly between SUPPLY MIN and SUPPLY MAX.
- Use PRIORITY 1 for DHW if it is used. Check that its values suit the application.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 3 boiler manual, p. 56. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.