Applies to: SVF 500/600 Series 1 boiler

Common causes of remove, inspect and clean the burner

  • Lint or sediment in the burner
  • Damaged burner insulation
  • Damaged or stretched gaskets

How to fix remove, inspect and clean the burner: step by step

  1. Use an 8 mm wrench or socket to remove the five M5 bolts holding the burner access hatch
  2. Remove the burner access hatch
  3. Use a 10 mm socket or wrench to remove the six M5 bolts securing the burner
  4. Pull the burner straight up and out; do not angle it, since that can damage the insulation
  5. Remove and discard the burner gasket
  6. Inspect the burner access hatch seal; if damaged, discard and use a new seal on reassembly
  7. Inspect the inside of the burner and brush or vacuum lint or sediment, or clean with a water spray from inside
  8. Inspect the burner exterior for damage
  9. Clean the underside of the burner flange with a soft brush to remove gasket fragments
  10. Set the burner aside and let it dry completely before reinstalling
  11. If insulation is damaged, replace it; if fragments fell into the heat exchanger, clean the heat exchanger thoroughly
  12. Replace any damaged or stretched gaskets before returning the boiler to service
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF 500/600 Series 1 boiler manual, p. 110. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.