Weil-McLain Boiler: Relief valve keeps opening (oil water boiler)
Relief valve keeps opening (oil water boiler) on a Weil-McLain boiler: Water discharges from the relief valve often.
Applies to: WGO-2 to WGO-9 oil-fired water boilers
Common causes of relief valve keeps opening (oil water boiler)
- Expansion tank too small
- Expansion tank waterlogged
How to fix relief valve keeps opening (oil water boiler): step by step
- Check the expansion tank. Recharge or replace a waterlogged tank.
- Check the tank size against the system and boiler water volume. An undersized tank lets pressure climb and lifts the relief valve.
- Check the relief valve per the label on it. Only test it if discharge piping is installed (scald risk).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain WGO Series 4 Water Boiler Manual 550-142-331/0225, Troubleshooting p.7; Controls requiring annual service p.29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.