Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Weil-McLain Boiler: Reinstall cover plate, blower, burner and igniter

Updated · by Aurora Star Tech Inc.

Reinstall cover plate, blower, burner and igniter on a Weil-McLain boiler: Reassembly after cleaning. Use a torque wrench and follow the torque values in the torque setting.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SVF 500/600 Series 1 boiler

Common causes of reinstall cover plate, blower, burner and igniter

  • Improperly seated gaskets
  • Over-torqued fasteners

How to fix reinstall cover plate, blower, burner and igniter: step by step

  1. Place the cover plate on the heat exchanger with the blower flange facing front and square
  2. Install all bolts finger-tight from the heat exchanger to the cover plate
  3. Tighten all bolts in a star pattern with a 5 mm Allen wrench to the torque in the torque setting
  4. Place the blower, venturi and gas valve assembly into the boiler; attach the blower to the cover plate and install the four nuts finger-tight, then torque them
  5. Reinstall the flex gas line to the inlet pipe with two pipe wrenches
  6. Reconnect the blower harnesses
  7. Insert a new burner gasket into the cover plate, set the burner in place and torque the six bolts in a star pattern
  8. Insert the burner access hatch seal and access cover; torque the five bolts
  9. Insert the ignition electrode with gasket; hand-tighten the two screws, then torque them
  10. Reattach the igniter cable and ground wire
  11. Reinstall the condensate trap to the heat exchanger drain and tighten the hose clamp
  12. Check the seal of the ignition electrode, igniter gasket and cover plate so they are gas-tight to prevent gas leaks or CO emissions
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF 500/600 Series 1 boiler manual, p. 112. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.