Weil-McLain Boiler: Radiant heating with zone valves, primary/secondary piping
Radiant heating with zone valves, primary/secondary piping on a Weil-McLain boiler: Typical radiant layout. The boiler works in condensing mode, so return water temperature does not need regulating. A high limit protects the radiant tubing.
Applies to: SF-550 and SF-750
How to fix radiant heating with zone valves, primary/secondary piping: step by step
- Size system piping and circulators for the flow and pressure drop needed.
- Add a high limit control (Fig. 10, item 22) set to protect the radiant tubing.
- Wire the high limit to the manual reset or automatic reset external limit circuit on the control.
- Install the flow/check valve on the boiler outlet.
- Provide an expansion tank per p. 14.
- Assign DHW and space heating priorities as needed. Priority 3 is the DHW choice when space heating has priority. The control will not run DHW in that case.
- Connect zone valve end switches to a space heating priority input (default Priority 2). Use isolation relays for 3-wire end switches.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.