Weil-McLain Boiler: Priority timing: MAX ON TIME and MIN ON TIME

Updated · by Aurora Star Tech Inc.

Priority timing: MAX ON TIME and MIN ON TIME on a Weil-McLain boiler: Each priority has its own settings. MAX ON TIME limits how long a priority runs before a lower priority's call takes over. MIN ON TIME is the shortest time a priority runs before a higher priority or the next lower priority can take over. Multiple inputs on the same priority run together when active. The boiler circulator output can be set per priority, and Blr Circ should be OFF for DHW piped directly with its own DHW circulator.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SF1000L/R, SF1500L/R, SF2000L/R

How to fix priority timing: max on time and min on time: step by step

  1. Use PRIORITY 1 for DHW when a DHW system is connected.
  2. Set MAX ON TIME and MIN ON TIME for each priority in the Wizard Priority Switching step or the priority menu.
  3. Set Blr Circ to OFF for DHW piped directly with its own DHW circulator.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 63. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.