Weil-McLain Boiler: Pipe a closed-type expansion tank
Pipe a closed-type expansion tank on a Weil-McLain boiler: Closed-type tanks rely on an air cushion that must stay in the system. Piping must allow that air to return to the tank.
Applies to: SlimFit 1000-2000 Series 2
Common causes of pipe a closed-type expansion tank
- Air trapped in horizontal piping
- Air lost through an automatic air vent, causing the tank to water-log
How to fix pipe a closed-type expansion tank: step by step
- Use Figure 15 (alternate) for closed-type tank connections.
- Pitch horizontal piping up toward the tank at 1 inch per 5 feet of run.
- Connect to the tank with at least 3/4-inch pipe so air can rise.
- Do not install an automatic air vent on a closed-type tank system.
- Do not use a closed-type tank if a connected water heater has an automatic vent.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 Boiler Manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.