Weil-McLain Boiler: Pilot lights but does not energize main gas valve(s)

Updated · by Aurora Star Tech Inc.

Pilot lights but does not energize main gas valve(s) on a Weil-McLain boiler: Pilot is burning but the control does not open the main gas valves.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: CGi-25 to CGi-8

Common causes of pilot lights but does not energize main gas valve(s)

  • Weak pilot flame signal
  • Flame rod corroded or wiring open
  • Pilot gas pressure too low at lower inlet pressures

How to fix pilot lights but does not energize main gas valve(s): step by step

  1. Check the pilot flame signal in control diagnostics. A signal below 60 is needed for a proven pilot.
  2. For burner ignition the flame signal must be below 25. If there is no signal or it is above 25, check the pilot flame sense wiring and flame rod for continuity and corrosion. Replace the rod if needed.
  3. If a pilot gas pressure regulator is used with low inlet pressure, raise the regulator setting to give the pilot more gas.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: CGi Series 5 boiler manual, p. 77. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.