Weil-McLain Boiler: Outdoor reset operation (supply temperature follows outdoor temperature)
Outdoor reset operation (supply temperature follows outdoor temperature) on a Weil-McLain boiler: Target supply temperature is set between Supply Min and Supply Max across an outdoor reset band.
Applies to: SlimFit Series 3 Control with outdoor sensor
How to fix outdoor reset operation (supply temperature follows outdoor temperature): step by step
- Set the desired supply temperatures for each space heating zone in its priority menu.
- Set Supply Max to the required supply water temperature at design maximum heat loss. Typical is 180°F for finned tube baseboard.
- Set Supply Min to the minimum desired supply water temperature. It can be set as low as 70°F.
- Set OD Reset Max to the outdoor temperature where the target reaches Supply Min. The factory default is 70°F.
- Set OD Reset Min to the outdoor temperature where the target reaches Supply Max. Set it equal to the outdoor design temperature (ODT) for the site. The factory default is 0°F.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SlimFit Series 3 boiler manual, p. 68. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.