Weil-McLain Boiler: Oil burner will not fire (steam boiler)
Oil burner will not fire (steam boiler) on a Weil-McLain boiler: Basic checks before calling it a burner problem. Do not keep hitting the reset on the primary control.
Applies to: SGO-3 to SGO-9 oil-fired steam boilers
Common causes of oil burner will not fire (steam boiler)
- Boiler service switch off, fuse blown or breaker tripped
- Thermostat set below room temperature
- Oil valves closed
- No water showing in the gauge glass (low water cutoff holding the burner off)
- Oil tank too low to feed the burner
How to fix oil burner will not fire (steam boiler): step by step
- Look in the combustion chamber first. If there is oil sitting in the chamber, do not fire the burner until it is cleaned out.
- Check power: service switch, fuse and breaker.
- Turn the thermostat up above room temperature.
- Make sure the oil valves are open and there is enough oil in the tank.
- Check that water is visible in the gauge glass. If not, fill to the water line marked on the jacket.
- Press the reset on the burner primary control one time only. Each extra press pumps more oil into the chamber and creates a fire hazard.
- Still no fire: move on to burner diagnostics (pump pressure, nozzle, ignition, cad cell) per the burner manual.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Start-up p.6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.