Weil-McLain Boiler: No heat: check demand, power and safeties
No heat: check demand, power and safeties on a Weil-McLain boiler: Work through these checks before replacing components when the boiler does not fire.
Applies to: SlimFit 1000-2000 MBH Series 2
Common causes of no heat: check demand, power and safeties
- No call for heat from thermostat, DHW aquastat or BMS
- Open external limit control
- Loose connector
- Gas pressure out of range or gas pressure switch tripped
How to fix no heat: check demand, power and safeties: step by step
- Space heating: confirm the thermostat is calling and its contacts, including zone controls, are closed. Check for 24 VAC between thermostat wire nuts and ground.
- DHW: confirm the tank aquastat is calling for heat.
- BMS systems: confirm the BMS is calling for heat.
- Confirm all external limit controls are installed and closed, or temporarily jumpered for testing.
- Confirm connectors to the control module are fully plugged in at the module and at the originating controls and harnesses.
- Confirm gas pressure matches page 45 and that gas pressure switches are not tripped.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 94. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.