Weil-McLain Boiler: No display and no boiler components operating
No display and no boiler components operating on a Weil-McLain boiler: Control is not receiving 120 V power.
Applies to: SVF 500/600 Series 1
Common causes of no display and no boiler components operating
- Service switch or circuit breaker off
- No 120 Vac supply at service switch
- Blown 4 A line voltage fuse
How to fix no display and no boiler components operating: step by step
- Turn on the service switch or reset the circuit breaker.
- Check for 120 Vac at the service switch. If absent, correct the supply.
- Check for 120 Vac at the line voltage terminal block J1 on the circuit board.
- Inspect the 4 A fuse and replace if necessary.
- If the fuse blows again, recheck wiring per diagrams.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 500/600 Series 1 Boiler Manual, p. 124. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.