Weil-McLain Boiler: No display and boiler will not respond to call for heat (no 24 V)
No display and boiler will not respond to call for heat (no 24 V) on a Weil-McLain boiler: Display is blank and the boiler does not respond to a call for heat. The control is not getting 24 V power.
Applies to: SlimFit 1000-2000 Series 2
Common causes of no display and boiler will not respond to call for heat (no 24 v)
- Short circuit or incorrect wiring
- Blown 3-amp low voltage fuse on control
- Failed transformer
How to fix no display and boiler will not respond to call for heat (no 24 v): step by step
- Check wiring for shorts or errors and correct per the wiring diagram, including transformer connection to the control.
- Check the 3-amp low voltage fuse on the control (see page 94) and replace with the proper part if blown.
- If the fuse blows again, recheck wiring per the diagram.
- Check for 24 VAC output at the transformer.
- Replace the transformer if it receives 120 VAC but outputs no 24 VAC.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 97. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.