Weil-McLain Boiler: Multiple zones with zone valves (24 V and isolation relay)
Multiple zones with zone valves (24 V and isolation relay) on a Weil-McLain boiler: Zone valves need a separate 24 V transformer sized for the total load of all valves. Do not wire 3-wire zone valves directly to the boiler T-T terminals. Use an isolation relay, which can damage boiler parts or cause unreliable operation if skipped.
Applies to: CGi-25 to CGi-8
Common causes of multiple zones with zone valves (24 v and isolation relay)
- 3-wire zone valves wired directly to T-T terminals
How to fix multiple zones with zone valves (24 v and isolation relay): step by step
- Install isolation (balancing) valves to balance the zones.
- Provide a separate 24 V transformer and size it for all zone valves connected.
- Do not wire 3-wire zone valves directly to the boiler T-T terminals.
- Install an isolation relay for 3-wire zone valves.
- Wire the zone valve end switch wires to the isolation relay coil.
- Wire the isolation relay contact across the boiler T-T terminals.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: CGi Series 5 boiler manual, p. 30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.