Weil-McLain Boiler: Metal flakes in the flue ways (oil water boiler)
Metal flakes in the flue ways (oil water boiler) on a Weil-McLain boiler: Corrosion or flaking in the flue passages.
Applies to: WGO-2 to WGO-9 oil-fired water boilers
Common causes of metal flakes in the flue ways (oil water boiler)
- Chemicals near the boiler (bleach, cleaners, sprays, fabric softener, paint remover) getting into combustion air
- Flue gas condensing in the flue ways
How to fix metal flakes in the flue ways (oil water boiler): step by step
- Remove those products from the boiler area.
- Check the nozzle and pump pressure for the right firing rate.
- Set combustion with an analyzer and clean the flue ways.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain WGO Series 4 Water Boiler Manual 550-142-331/0225, Troubleshooting p.7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.