Weil-McLain Boiler: Metal flakes in the flue passages
Metal flakes in the flue passages on a Weil-McLain boiler: Flakes of metal are found in the flueways. Either chemicals in the combustion air are attacking the boiler, or flue gas is condensing because the burner is not set right.
Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers
Common causes of metal flakes in the flue passages
- Combustion air contaminated by chemicals (bleach, cleaners, sprays, fabric softener, paint remover)
- Flue gas condensing in the boiler
How to fix metal flakes in the flue passages: step by step
- Look for chemicals stored near the boiler and remove them.
- Check that the nozzle is the right size and that the oil pump pressure gives the correct firing rate.
- Set combustion with an analyzer.
- Clean the flueways after the cause is fixed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Troubleshooting, p.7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.