Weil-McLain Boiler: Low water cut-off (LWCO) test
Low water cut-off (LWCO) test on a Weil-McLain boiler: The LWCO is built into the Boiler Out sensor at the highest point of the heat exchanger. Two test methods are given.
Applies to: SVF 500/600 boilers, LWCO sensor on connector J9
How to fix low water cut-off (lwco) test: step by step
- Method 1: press and hold the gray LWCO test button below the J8 and J9 connectors for at least 5 seconds.
- Method 2: turn off the boiler and the circulating pump (if used), isolate the boiler and drain the water level below the LWCO sensor.
- For method 2, turn the boiler on. It should not run and should show a Low Water fault.
- Expected result for either method: a manual lockout reset with LOW WATER on the display.
- If water was drained, turn the boiler off, refill the system, restart the pump if used, turn the boiler on, then reset from the display Reset button.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF 500/600 boiler manual, p. 114. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.