Weil-McLain Boiler: Low temperature systems: choose the piping method
Low temperature systems: choose the piping method on a Weil-McLain boiler: For radiant or converted gravity systems, primary/secondary piping is preferred because it keeps the heating circuit flow independent of boiler bypass adjustment. Other options are boiler bypass (Figures 21 and 22) and system bypass (Figure 23). System bypass does not control radiant supply temperature, so it is not used for radiant systems.
Applies to: CGi-25 to CGi-8
Common causes of low temperature systems: choose the piping method
- Return water below 130°F causing corrosion of sections or burners
How to fix low temperature systems: choose the piping method: step by step
- Use primary/secondary piping (Figure 19 or 20) when possible.
- If primary/secondary cannot be used, use boiler bypass piping (Figure 21 or 22).
- Use system bypass (Figure 23) only for converted gravity systems where reduced flow will not cause heat distribution problems.
- Do not use system bypass for radiant systems.
- If radiant tubing has no oxygen barrier, use a heat exchanger.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: CGi Series 5 boiler manual, p. 30-31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.