Weil-McLain Boiler: Low-temperature system: primary/secondary bypass valve setup
Low-temperature system: primary/secondary bypass valve setup on a Weil-McLain boiler: Preferred piping for radiant or converted gravity systems. Bypass valves 7a and 7b mix hot boiler outlet water with system return water so the boiler return stays at or above 130°F. Setting is done with the system cold.
Applies to: CGi-25 to CGi-8 low-temperature systems, primary/secondary piping (Figures 19 and 20)
How to fix low-temperature system: primary/secondary bypass valve setup: step by step
- Set the valves while the system is cool, for the coldest expected water temperature (usually 60°F).
- Start with valve 7a fully closed and valve 7b fully open.
- Slowly open valve 7a while closing valve 7b until gauge 8 reads 130°F when gauge 4a reads 60°F.
- Confirm gauge 4b is installed on radiant systems so supply temperature to the tubing can be seen.
- If gauge 8 is not installed, adjust until the boiler-mounted temperature/pressure gauge reads at least 150°F with cold return water (about 60°F).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain CGi Series 5 boiler manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.