Weil-McLain Boiler: Low-temperature system: boiler-bypass piping valve setup
Low-temperature system: boiler-bypass piping valve setup on a Weil-McLain boiler: Used on converted gravity or radiant systems when primary/secondary piping cannot be applied. Part of the circulator flow is bypassed around the boiler to raise average boiler water temperature and prevent flue gas condensation.
Applies to: CGi-25 to CGi-8 converted gravity or radiant systems (Figures 21 and 22)
How to fix low-temperature system: boiler-bypass piping valve setup: step by step
- Start with valve 7a fully closed and valve 7b fully open.
- Slowly open valve 7a while closing valve 7b until gauge 8 reads 60°F higher than gauge 4a.
- If gauge 4a is not installed, set the valves with cold return water, assume 60°F return, and set gauge 8 to at least 120°F.
- Remember valve 7a sets system flow rate and valve 7b sets boiler flow rate.
- The boiler-mounted temperature/pressure gauge can replace a separate gauge 8.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain CGi Series 5 boiler manual, p. 34. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.