Weil-McLain Boiler: Lock-up gas pressure regulator when inlet can exceed 14 in W.C.
Lock-up gas pressure regulator when inlet can exceed 14 in W.C. on a Weil-McLain boiler: Protect the boiler gas valve and pressure switches from high supply pressure.
Applies to: SVF 500/600 natural gas or propane supply lines
Common causes of lock-up gas pressure regulator when inlet can exceed 14 in w.c.
- Inlet gas pressure can rise above 14 in W.C.
How to fix lock-up gas pressure regulator when inlet can exceed 14 in w.c.: step by step
- If inlet pressure can exceed 14 in W.C. at any time, install a 100% lock-up gas pressure regulator per ANSI Z21.80 in the gas supply line.
- Expect lock-up regulator pressure spikes of 5 in W.C. or 150% of setting, whichever is greater.
- With the boiler at minimum input rate, adjust the lock-up regulator so inlet pressure is below 10 in W.C. This leaves a margin below the high gas pressure switch setting.
- Adjust gas pressure higher or lower as needed within the limits of the system.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 62. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.