Weil-McLain Boiler: Install vent and air adapters, gaskets and clamps
Install vent and air adapters, gaskets and clamps on a Weil-McLain boiler: Installer supplies the manufacturer's SlimFit Vent/Air Adapter for the vent and air connections. Reducers are added as needed for the pipe size used.
Applies to: SlimFit 1000-2000 Series 2
Common causes of install vent and air adapters, gaskets and clamps
- Gasket installed backward
- Clamp over-tightened and deforming the plastic connector
- Vent pipe size not matched to the adapter
How to fix install vent and air adapters, gaskets and clamps: step by step
- Install a vent pipe manufacturer's SlimFit Vent/Air Adapter at the boiler vent connection and at the air connection, if used.
- Use the pipe maker's reducers where needed to match the vent or air pipe size.
- Check the gasket: the barbed band must point DOWN.
- Tighten the vent connection clamp securely, but do not over-tighten it.
- Confirm the clamp band does not deform or dig into the plastic vent connector.
- Get part and kit numbers from Figure 96 (page 105).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit Series 2 Boiler Manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.