Weil-McLain Boiler: Install propane blower plate on SF-750
Install propane blower plate on SF-750 on a Weil-McLain boiler: The SF-750 natural gas unit has no blower plate. The propane version needs the plate and gaskets shipped with the boiler.
Applies to: SF-750 propane only
How to fix install propane blower plate on sf-750: step by step
- Turn off all power to the boiler.
- Disconnect the two wiring connectors on the blower.
- Disconnect the blower flange from the mixing tube flange and support the blower and gas train.
- Check that the plate reads "750 LP".
- Fit one gasket on each side of the blower plate, then position the blower.
- Start the nuts on the top two bolts, then the bottom two, without tearing the gasket.
- Torque the flange bolts to 15 N-m / 132 in-lbs / 11 ft-lbs, without over-tightening.
- Reconnect the two blower harnesses and reinstall the front door.
- Restore power, open the manual gas valve, check for leaks, then adjust combustion and run startup.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit 550/750 Series 3 boiler manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.