Weil-McLain Boiler: Install direct vent sidewall air and vent terminations
Install direct vent sidewall air and vent terminations on a Weil-McLain boiler: Sidewall direct vent uses corrosion-resistant stop plates sized just over the pipe diameter, sourced only from the vent pipe manufacturer. Vent and air pipe shoulders must rest against the outer stop plates so the pipes cannot be pushed inward. Exposed pipe up to 4 ft needs bracing every 24 in. Longer exposed runs need an insulated enclosure with terminations exiting through it. Seal all exterior openings with exterior caulk and fit bird screens to both terminal elbows.
Applies to: SlimFit SF1000L/R, SF1500L/R, SF2000L/R direct vent sidewall installations
How to fix install direct vent sidewall air and vent terminations: step by step
- Cut the vent pipe hole. For combustible walls, make it at least 3/8 in larger than the vent pipe; for noncombustible walls, follow the vent maker's sizing.
- Install a corrosion-resistant metal thimble in the vent hole and follow local code for wall penetrations.
- Fit the outer stop plates (hole just larger than pipe) from the vent maker only.
- Insert the last vent and air lengths from outside until the female shoulders seat against the stop plates.
- Attach the outward-facing 90-degree vent elbow and the down-turned 90-degree air elbow.
- Brace the exposed pipe every 24 in or closer; leave no more than 4 ft exposed without an enclosure.
- Install bird screens in both terminal elbows and seal exterior openings with exterior caulk.
- For multiple boiler terminations, follow the spacing shown in the manual's multiple termination figure.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.