Weil-McLain Boiler: Inspect the ignition electrode and wiring

Updated · by Aurora Star Tech Inc.

Inspect the ignition electrode and wiring on a Weil-McLain boiler: Igniter and flame sense assembly inspection and cleaning. Boiler must be cold and the gas shut off first.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SVF 500/600 Series 1 boiler

Common causes of inspect the ignition electrode and wiring

  • White oxide buildup on the ignition electrode
  • Cracked or damaged igniter
  • Worn or damaged ignition cable or ground wire

How to fix inspect the ignition electrode and wiring: step by step

  1. Shut off power to the boiler
  2. Close the external manual gas valve
  3. Let the boiler cool to room temperature if it has been firing
  4. Disconnect the ground wire and ignition cable from the ignition electrode
  5. Use a 3 mm Allen wrench to remove the two screws holding the electrode to the cover plate, then carefully remove the igniter with flame sense assembly
  6. Discard the ignition electrode gasket
  7. Remove white oxides from the electrode with steel wool; clean the gasket surfaces on the igniter flange and the cover plate mating surface
  8. Replace the igniter if it is cracked or damaged or cannot be cleaned properly
  9. Slide a new gasket onto the electrode and set the assembly aside
  10. Check ignition cable resistance (see the electrical check setting)
  11. Verify all wiring is in good condition and securely attached
  12. Check the ground wire from the heat exchanger access cover to the control tray ground screw (see the electrical check setting); replace the ground wire if results are not satisfactory
  13. Confirm the igniter rods are parallel and set the spark gap as specified (see notes)
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF 500/600 Series 1 boiler manual, p. 109. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.