Weil-McLain Boiler: Improper pilot burner flame
Improper pilot burner flame on a Weil-McLain boiler: A proper pilot is a blue flame, with the inner cone engulfing the pilot flame sensor and the sensor glowing cherry red. Compare the flame to these faults.
Applies to: Spark-ignited pilot CGi Series 5 boilers
Common causes of improper pilot burner flame
- Overfired: large flame lifting or blowing past the pilot flame sensor
- Underfired: small flame with the inner cone not engulfing the sensor
- Lack of primary air: yellow tip on the flame
How to fix improper pilot burner flame: step by step
- Check the flame against the proper pilot flame description.
- For an overfired or underfired pilot, adjust the gas supply to the pilot and recheck.
- For a yellow flame tip, check and correct primary air supply, then recheck.
- Confirm the pilot flame sensor glows cherry red once the flame is correct.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain CGi Series 5 boiler manual, p. 65. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.