Weil-McLain Boiler: High flow DHW circuit with secondary connection
High flow DHW circuit with secondary connection on a Weil-McLain boiler: Use this when DHW flow is higher than the boiler allows or the DHW coil has high pressure drop. DHW flows only through the secondary connection piping.
Applies to: High flow DHW circuits
How to fix high flow dhw circuit with secondary connection: step by step
- Size the secondary connection piping (no more than 8 pipe diameters apart) for the full DHW flow.
- Install a system circulator sized for the required flow and head.
- Install the flow/check valve on the boiler outlet to prevent gravity circulation during DHW heating.
- Size the boiler loop piping at least to the minimum in the pipe sizing table.
- Do not use a closed-type tank if the water heater has an automatic vent.
- Use the Advanced Manual to set the boiler pump to run during DHW demand, if needed. DHW as a zone does not apply to this setup.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SlimFit 550/750 Series 3 boiler manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.